Electrical Testing & Inspection

Ultrasound, partial discharge, de-energized testing, grounding verification, and full asset inventories — the deep diagnostics behind a serious maintenance program.

Call 208-991-0122 Request a No-Cost Survey

Testing Services

● Insulation Resistance (IR) Testing ● DLRO / Micro-Ohm Testing ● Ultrasonic Inspection ● Infrared Thermography
Energized Testing

Ultrasound & partial discharge detection

Some failures make noise before they make heat. Arcing, surface tracking, and corona discharge all emit high-frequency sound — inaudible to you, unmistakable to an ultrasonic instrument. Because sound travels through and around enclosures, ultrasound screening finds developing faults inside closed switchgear without opening a single cover.

Partial discharge — insulation breaking down microscopically under electrical stress — is the classic slow killer of medium-voltage gear. Caught early, it's a planned repair; caught late, it's a failed bus and a dark building. We screen for it as part of energized inspection rounds, pairing every ultrasound finding with infrared and electrical verification.

  • Airborne & structure-borne ultrasound inspection
  • Partial discharge screening on MV equipment
  • Enclosed gear inspected without opening covers
  • Findings verified, rated & documented
Ultrasonic inspection detecting a partial discharge signature inside closed switchgear
Shutdown Maintenance

De-energized testing & preventive maintenance

Some questions can only be answered with the power off: Is the insulation still sound? Are the contacts still low-resistance? Will this breaker actually trip when asked? During planned shutdown windows we clean, inspect, torque, exercise, and electrically test your critical equipment — the hands-on maintenance that energized scanning can't replace.

Breakers are the sleeper issue here. A breaker that has sat closed for ten years may be seized, slow, or miscalibrated — and every arc flash calculation and coordination study assumes it works to spec. Exercising and testing protective devices is some of the highest-value maintenance a facility can buy.

Insulation resistance test reading 2.5 gigohms at 1000 VDC — pass
Know What You Have

Equipment asset inventory & condition assessment

Ask most facility managers for a complete list of their electrical distribution equipment and its condition, and the honest answer is a shrug — drawings are decades old, labels are missing, and institutional memory retired two managers ago. Yet that list is the foundation of every maintenance decision, every budget, and NFPA 70B's required Electrical Maintenance Program.

We build it for you. Every panel, breaker, transformer, disconnect, and motor control is identified, labeled, photographed, and rated for condition and criticality. From there, maintenance intervals and testing scopes practically write themselves — and your program documentation is audit-ready from day one.

  • Complete distribution equipment inventory
  • Labeling & photo documentation
  • Condition & criticality ratings per asset
  • The backbone of NFPA 70B EMP documentation
START WITH A NO-COST SURVEY
Condition-rated electrical asset register with labeled equipment and service dates

Frequently Asked Questions

What's the difference between energized and de-energized testing?

Energized testing — infrared, ultrasound, power monitoring — happens while your facility runs and finds problems by their symptoms: heat, sound, and electrical signature. De-energized testing happens during a planned shutdown and measures the equipment itself: insulation resistance, contact resistance, torque, and mechanical operation. A complete program uses both.

How much shutdown time does de-energized testing take?

Less than most facilities fear. Work is scoped per-section so we test in planned windows — nights, weekends, or holiday shutdowns — and your system is inspected, tested, and back online on a schedule agreed in advance.

What is ultrasound inspection listening for?

Arcing, tracking, and corona each produce distinctive high-frequency sound before they produce visible damage. With enclosed switchgear, ultrasound often detects a developing fault that a thermal camera can't see through the enclosure — which is why the two are used together.

Why does the equipment inventory matter so much?

Because everything else builds on it. NFPA 70B's Electrical Maintenance Program starts with knowing what equipment you have and what condition it's in; maintenance intervals, testing scope, and budgeting all flow from that list. Most facilities are surprised by how much undocumented gear the first survey finds.

Can you test our grounding system?

Yes. Ground resistance and bonding verification confirm that the path protecting your people and equipment actually performs — a frequent weak point in older facilities and a standard part of a full testing program.

More Ways We Help

● TEGG Program ● Infrared Thermography ● Arc Flash Studies ● Power Quality ● Testing & Inspection ● NFPA 70B ● NFPA 70E
See All Services
⚡

READY TO PROTECT YOUR FACILITY?

Start with a no-cost, no-obligation survey: we'll walk your electrical system, give you a written proposal for your testing program, and include the replacement cost of your electrical distribution — so you know exactly what's at stake.

☎ CALL NOW NO-COST SURVEY